Error codes – κωδικοί βλαβών κλιματιστικά AIRWELL (AWSI-HZDE , AWAU-YBZE)

Error codes – κωδικοί βλαβών κλιματιστικά AIRWELL

 

Indoor Units: AWSI-HZDE009-H11 , AWSI-HZDE012-H11 , AWSI-HZDE018-H11

Outdoor Units: AWAU-YBZE218-H11 , AWAU-YBZE324-H11 , AWAU-YBZE430-H11

Display
Blinking

RUN
Blinking

COOL
Blinking

HEAT
Fault description
Reason

E1

1
   
HP switch protection
Refrigerant was superabundant. Poor heat exchange (including blockage and bad radiating environment). Too high ambient temperature

E2

2
   
Indoor coil defrost Protection
Poor air-return in indoor unit. Fan speed is abnormal. Evaporator is dirty.

E4

4
   
Compressor over Heating Protection
Electronic Expansion Valve connection problem or damage. Refrigerant leakage. Poor heat exchange

E5

5
   
AC Over current protection
Supply voltage is unstable. Supply voltage is too low and load is too high

E6

6
   
Communication malfunction
Wiring mistakes Indoor Unit or Outdoor Unit PCB problem

E7

7
   
Mode conflict
Mode conflict to other Indoor Unit

E8

8
   
Indoor , Outdoor coil over heating protection
Too high ambient temperature. Poor heat exchange (including blockage and bad radiating environment)

H6

11
   
No feedback of indoor motor
IFAN motor damaged. IFAN motor blocked. Indoor Unit PCB problem

C5

15
   
Malfunction protection of jumper cap
Poor connection of the jumper on indoor PCB.

U8

17
   
Zero-crossing protection (Indoor Unit)
IFAN motor damaged. Zero-crossing circuit damaged on Indoor Unit PCB

LP

19
   
Mismatch of Indoor Unit and Outdoor Unit
 

F1

 
1
 
RAT failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

F2

 
2
 
Indoor Coil Temperature (RT2) sensor failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

F3

 
3
 
Outdoor Air Temperature sensor failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

F5

 
5
 
Compressor Top Temperature sensor failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

PH

 
11
 
DC over voltage
AC input voltage is too high. Reactor has problem. Outdoor Unit PCB has problem

F4

 
18
 
Outdoor Coil Temperature sensor failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

b5

 
19
 
RLT failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

b7

 
22
 
Return Gas Temperature sensor failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

H3

   
3
Compressor overload

protection
Electronic Expansion Valve connection problem or damaged. Refrigerant leakage. OLP damaged

H5

   
5
IPM protection
Abnormal power input voltage. Compressor wiring mistake. Liquid and gas valve are not open. Electronic Expansion Valve damaged or not proper working. Poor heat exchange. Over charged system.

HC

   
6
Power Factor Corrector protection
PFC module assembly problem. Poor heat exchange of Heatsink Power Factor Corrector reactor problem. Abnormal power voltage. Power Factor Corrector circuit problem on PCB

H7

   
7
Desynchronizing of

compressor
Abnormal power input voltage. Compressor wiring mistake. Liquid and gas valve are not open. Electronic Expansion Valve damaged or not proper working. Poor heat exchange. Over charged system.

Lc

   
11
Compressor start up failure
Compressor wiring mistake. Over charged system. System not balanced before compressor starting. Compressor problem

U1

   
12
Compressor phase current detection problem
Phase current detection circuit for compressor has problem.

P5

   
15
DC over current
Abnormal power input voltage. Compressor wiring mistake. Liquid and gas valve are not open. Electronic Expansion Valve damaged or not proper working Poor heat exchange. Over charged system.

PU

   
17
Charging malfunction of capacitor
Reactor open. Charging relay or other components damaged on PCB.

P7

   
18
Heat Sink Temperature sensor failure
Sensor was broken or damaged. PCB temperature detection circuit has problem

P8

   
19
Heat Sink Temperature sensor over heating protection
Insufficient attachment of IPM module to Heatsink. Outdoor PCB problem.

PL

   
21
DC under voltage
AC input voltage is too low. Reactor has problem. Outdoor Unit PCB has problem

Ld

     
Lack Phase Protection of Compressor
Compressor wiring problem. Compressor problem. IPM module problem or compressor current detection circuit has problem. Compressor malfunction due to Electronic Expansion Valve problem
           